Line data Source code
1 : // EnergyPlus, Copyright (c) 1996-2025, The Board of Trustees of the University of Illinois,
2 : // The Regents of the University of California, through Lawrence Berkeley National Laboratory
3 : // (subject to receipt of any required approvals from the U.S. Dept. of Energy), Oak Ridge
4 : // National Laboratory, managed by UT-Battelle, Alliance for Sustainable Energy, LLC, and other
5 : // contributors. All rights reserved.
6 : //
7 : // NOTICE: This Software was developed under funding from the U.S. Department of Energy and the
8 : // U.S. Government consequently retains certain rights. As such, the U.S. Government has been
9 : // granted for itself and others acting on its behalf a paid-up, nonexclusive, irrevocable,
10 : // worldwide license in the Software to reproduce, distribute copies to the public, prepare
11 : // derivative works, and perform publicly and display publicly, and to permit others to do so.
12 : //
13 : // Redistribution and use in source and binary forms, with or without modification, are permitted
14 : // provided that the following conditions are met:
15 : //
16 : // (1) Redistributions of source code must retain the above copyright notice, this list of
17 : // conditions and the following disclaimer.
18 : //
19 : // (2) Redistributions in binary form must reproduce the above copyright notice, this list of
20 : // conditions and the following disclaimer in the documentation and/or other materials
21 : // provided with the distribution.
22 : //
23 : // (3) Neither the name of the University of California, Lawrence Berkeley National Laboratory,
24 : // the University of Illinois, U.S. Dept. of Energy nor the names of its contributors may be
25 : // used to endorse or promote products derived from this software without specific prior
26 : // written permission.
27 : //
28 : // (4) Use of EnergyPlus(TM) Name. If Licensee (i) distributes the software in stand-alone form
29 : // without changes from the version obtained under this License, or (ii) Licensee makes a
30 : // reference solely to the software portion of its product, Licensee must refer to the
31 : // software as "EnergyPlus version X" software, where "X" is the version number Licensee
32 : // obtained under this License and may not use a different name for the software. Except as
33 : // specifically required in this Section (4), Licensee shall not use in a company name, a
34 : // product name, in advertising, publicity, or other promotional activities any name, trade
35 : // name, trademark, logo, or other designation of "EnergyPlus", "E+", "e+" or confusingly
36 : // similar designation, without the U.S. Department of Energy's prior written consent.
37 : //
38 : // THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDERS AND CONTRIBUTORS "AS IS" AND ANY EXPRESS OR
39 : // IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY
40 : // AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE COPYRIGHT OWNER OR
41 : // CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR
42 : // CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR
43 : // SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY
44 : // THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR
45 : // OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE
46 : // POSSIBILITY OF SUCH DAMAGE.
47 :
48 : // C++ Headers
49 : #include <cmath>
50 :
51 : // ObjexxFCL Headers
52 : #include <ObjexxFCL/Array.functions.hh>
53 : #include <ObjexxFCL/Fmath.hh>
54 :
55 : // EnergyPlus Headers
56 : #include <EnergyPlus/Autosizing/Base.hh>
57 : #include <EnergyPlus/BranchNodeConnections.hh>
58 : #include <EnergyPlus/Data/EnergyPlusData.hh>
59 : #include <EnergyPlus/DataDefineEquip.hh>
60 : #include <EnergyPlus/DataEnvironment.hh>
61 : #include <EnergyPlus/DataHVACGlobals.hh>
62 : #include <EnergyPlus/DataLoopNode.hh>
63 : #include <EnergyPlus/DataSizing.hh>
64 : #include <EnergyPlus/DataZoneEnergyDemands.hh>
65 : #include <EnergyPlus/DataZoneEquipment.hh>
66 : #include <EnergyPlus/FluidProperties.hh>
67 : #include <EnergyPlus/General.hh>
68 : #include <EnergyPlus/GeneralRoutines.hh>
69 : #include <EnergyPlus/HVACSingleDuctInduc.hh>
70 : #include <EnergyPlus/InputProcessing/InputProcessor.hh>
71 : #include <EnergyPlus/MixerComponent.hh>
72 : #include <EnergyPlus/NodeInputManager.hh>
73 : #include <EnergyPlus/OutputProcessor.hh>
74 : #include <EnergyPlus/OutputReportPredefined.hh>
75 : #include <EnergyPlus/Plant/DataPlant.hh>
76 : #include <EnergyPlus/PlantUtilities.hh>
77 : #include <EnergyPlus/Psychrometrics.hh>
78 : #include <EnergyPlus/ScheduleManager.hh>
79 : #include <EnergyPlus/UtilityRoutines.hh>
80 : #include <EnergyPlus/WaterCoils.hh>
81 :
82 : namespace EnergyPlus {
83 :
84 : namespace HVACSingleDuctInduc {
85 :
86 : // Module containing routines dealing terminal 4 pipe induction terminal units
87 :
88 : // MODULE INFORMATION:
89 : // AUTHOR Fred Buhl
90 : // DATE WRITTEN June 15 2004
91 : // MODIFIED Brent Griffith, Sept 2010, plant upgrades, fluid props
92 :
93 : // PURPOSE OF THIS MODULE:
94 : // To encapsulate the data and algorithms needed to simulate 4 pipe induction terminal units
95 :
96 : // METHODOLOGY EMPLOYED:
97 : // The terminal boxes are modeled as compound components: heating coil, cooling coil and
98 : // mixer. The combined components are controlled to meet the zone load.
99 :
100 0 : void SimIndUnit(EnergyPlusData &state,
101 : std::string_view CompName, // name of the terminal unit
102 : bool const FirstHVACIteration, // TRUE if first HVAC iteration in time step
103 : int const ZoneNum, // index of zone served by the terminal unit
104 : int const ZoneNodeNum, // zone node number of zone served by the terminal unit
105 : int &CompIndex // which terminal unit in data structure
106 : )
107 : {
108 :
109 : // SUBROUTINE INFORMATION:
110 : // AUTHOR Fred Buhl
111 : // DATE WRITTEN June 18 2004
112 :
113 : // PURPOSE OF THIS SUBROUTINE:
114 : // Manages the simulation of a passive (no fan) induction terminal unit.
115 : // Called from SimZoneAirLoopEquipment in module ZoneAirLoopEquipmentManager.
116 :
117 : // SUBROUTINE LOCAL VARIABLE DECLARATIONS:
118 : int IUNum; // index of terminal unit being simulated
119 :
120 : // First time SimIndUnit is called, get the input for all the passive terminal induction units
121 0 : if (state.dataHVACSingleDuctInduc->GetIUInputFlag) {
122 0 : GetIndUnits(state);
123 0 : state.dataHVACSingleDuctInduc->GetIUInputFlag = false;
124 : }
125 :
126 : // Get the induction unit index
127 0 : if (CompIndex == 0) {
128 0 : IUNum = Util::FindItemInList(CompName, state.dataHVACSingleDuctInduc->IndUnit);
129 0 : if (IUNum == 0) {
130 0 : ShowFatalError(state, format("SimIndUnit: Induction Unit not found={}", CompName));
131 : }
132 0 : CompIndex = IUNum;
133 : } else {
134 0 : IUNum = CompIndex;
135 0 : if (IUNum > state.dataHVACSingleDuctInduc->NumIndUnits || IUNum < 1) {
136 0 : ShowFatalError(state,
137 0 : format("SimIndUnit: Invalid CompIndex passed={}, Number of Induction Units={}, System name={}",
138 : CompIndex,
139 0 : state.dataHVACSingleDuctInduc->NumIndUnits,
140 : CompName));
141 : }
142 0 : if (state.dataHVACSingleDuctInduc->CheckEquipName(IUNum)) {
143 0 : if (CompName != state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name) {
144 0 : ShowFatalError(state,
145 0 : format("SimIndUnit: Invalid CompIndex passed={}, Induction Unit name={}, stored Induction Unit for that index={}",
146 : CompIndex,
147 : CompName,
148 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
149 : }
150 0 : state.dataHVACSingleDuctInduc->CheckEquipName(IUNum) = false;
151 : }
152 : }
153 :
154 0 : auto &indUnit = state.dataHVACSingleDuctInduc->IndUnit(IUNum);
155 :
156 0 : state.dataSize->CurTermUnitSizingNum = state.dataDefineEquipment->AirDistUnit(indUnit.ADUNum).TermUnitSizingNum;
157 : // initialize the unit
158 0 : InitIndUnit(state, IUNum, FirstHVACIteration);
159 :
160 0 : state.dataSize->TermUnitIU = true;
161 :
162 : // Select the correct unit type
163 0 : switch (indUnit.UnitType_Num) {
164 0 : case SingleDuct_CV::FourPipeInduc: {
165 0 : SimFourPipeIndUnit(state, IUNum, ZoneNum, ZoneNodeNum, FirstHVACIteration);
166 0 : } break;
167 0 : default: {
168 0 : ShowSevereError(state, format("Illegal Induction Unit Type used={}", indUnit.UnitType));
169 0 : ShowContinueError(state, format("Occurs in Induction Unit={}", indUnit.Name));
170 0 : ShowFatalError(state, "Preceding condition causes termination.");
171 0 : } break;
172 : }
173 :
174 0 : state.dataSize->TermUnitIU = false;
175 :
176 : // the tasks usually done by the Update and Report routines are not required in a compound terminal unit.
177 :
178 : // Update the current unit's outlet nodes. No update needed
179 :
180 : // Fill the report variables. There are no report variables
181 0 : indUnit.ReportIndUnit(state);
182 0 : }
183 :
184 1 : void GetIndUnits(EnergyPlusData &state)
185 : {
186 :
187 : // SUBROUTINE INFORMATION:
188 : // AUTHOR Fred Buhl
189 : // DATE WRITTEN June 15 2004
190 :
191 : // PURPOSE OF THIS SUBROUTINE:
192 : // Obtains input data for passive induction air terminal units and stores it in the
193 : // induction terminal unit data structures
194 :
195 : // METHODOLOGY EMPLOYED:
196 : // Uses "Get" routines to read in data.
197 :
198 : // SUBROUTINE PARAMETER DEFINITIONS:
199 : static constexpr std::string_view RoutineName("GetIndUnits "); // include trailing blank space
200 : static constexpr std::string_view routineName = "GetIndUnits";
201 :
202 1 : Array1D_string Alphas; // Alpha input items for object
203 1 : Array1D_string cAlphaFields; // Alpha field names
204 1 : Array1D_string cNumericFields; // Numeric field names
205 1 : Array1D<Real64> Numbers; // Numeric input items for object
206 1 : Array1D_bool lAlphaBlanks; // Logical array, alpha field input BLANK = .TRUE.
207 1 : Array1D_bool lNumericBlanks; // Logical array, numeric field input BLANK = .TRUE.
208 1 : int NumAlphas(0); // Number of Alphas for each GetObjectItem call
209 1 : int NumNumbers(0); // Number of Numbers for each GetObjectItem call
210 1 : int TotalArgs(0); // Total number of alpha and numeric arguments (max) for a
211 : // certain object in the input file
212 : int IOStatus; // Used in GetObjectItem
213 1 : bool ErrorsFound(false); // Set to true if errors in input, fatal at end of routine
214 :
215 : // find the number of each type of induction unit
216 1 : std::string CurrentModuleObject = "AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction";
217 1 : state.dataHVACSingleDuctInduc->NumFourPipes = state.dataInputProcessing->inputProcessor->getNumObjectsFound(state, CurrentModuleObject);
218 1 : state.dataHVACSingleDuctInduc->NumIndUnits = state.dataHVACSingleDuctInduc->NumFourPipes;
219 : // allocate the data structures
220 1 : state.dataHVACSingleDuctInduc->IndUnit.allocate(state.dataHVACSingleDuctInduc->NumIndUnits);
221 1 : state.dataHVACSingleDuctInduc->CheckEquipName.dimension(state.dataHVACSingleDuctInduc->NumIndUnits, true);
222 :
223 1 : state.dataInputProcessing->inputProcessor->getObjectDefMaxArgs(state, CurrentModuleObject, TotalArgs, NumAlphas, NumNumbers);
224 :
225 1 : Alphas.allocate(NumAlphas);
226 1 : cAlphaFields.allocate(NumAlphas);
227 1 : cNumericFields.allocate(NumNumbers);
228 1 : Numbers.dimension(NumNumbers, 0.0);
229 1 : lAlphaBlanks.dimension(NumAlphas, true);
230 1 : lNumericBlanks.dimension(NumNumbers, true);
231 :
232 : // loop over Series PIUs; get and load the input data
233 2 : for (int IUIndex = 1; IUIndex <= state.dataHVACSingleDuctInduc->NumFourPipes; ++IUIndex) {
234 :
235 1 : state.dataInputProcessing->inputProcessor->getObjectItem(state,
236 : CurrentModuleObject,
237 : IUIndex,
238 : Alphas,
239 : NumAlphas,
240 : Numbers,
241 : NumNumbers,
242 : IOStatus,
243 : lNumericBlanks,
244 : lAlphaBlanks,
245 : cAlphaFields,
246 : cNumericFields);
247 :
248 1 : ErrorObjectHeader eoh{routineName, CurrentModuleObject, Alphas(1)};
249 :
250 1 : int IUNum = IUIndex;
251 1 : Util::IsNameEmpty(state, Alphas(1), CurrentModuleObject, ErrorsFound);
252 :
253 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name = Alphas(1);
254 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType = CurrentModuleObject;
255 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType_Num = SingleDuct_CV::FourPipeInduc;
256 :
257 1 : if (lAlphaBlanks(2)) {
258 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).availSched = Sched::GetScheduleAlwaysOn(state);
259 1 : } else if ((state.dataHVACSingleDuctInduc->IndUnit(IUNum).availSched = Sched::GetSchedule(state, Alphas(2))) == nullptr) {
260 0 : ShowSevereItemNotFound(state, eoh, cAlphaFields(2), Alphas(2));
261 0 : ErrorsFound = true;
262 : }
263 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow = Numbers(1);
264 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio = Numbers(2);
265 1 : if (lNumericBlanks(2)) {
266 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio = 2.5;
267 : }
268 :
269 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).PriAirInNode =
270 1 : GetOnlySingleNode(state,
271 1 : Alphas(3),
272 : ErrorsFound,
273 : DataLoopNode::ConnectionObjectType::AirTerminalSingleDuctConstantVolumeFourPipeInduction,
274 1 : Alphas(1),
275 : DataLoopNode::NodeFluidType::Air,
276 : DataLoopNode::ConnectionType::Inlet,
277 : NodeInputManager::CompFluidStream::Primary,
278 : DataLoopNode::ObjectIsParent,
279 1 : cAlphaFields(3));
280 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).SecAirInNode =
281 1 : GetOnlySingleNode(state,
282 1 : Alphas(4),
283 : ErrorsFound,
284 : DataLoopNode::ConnectionObjectType::AirTerminalSingleDuctConstantVolumeFourPipeInduction,
285 1 : Alphas(1),
286 : DataLoopNode::NodeFluidType::Air,
287 : DataLoopNode::ConnectionType::Inlet,
288 : NodeInputManager::CompFluidStream::Primary,
289 : DataLoopNode::ObjectIsParent,
290 1 : cAlphaFields(4));
291 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode =
292 1 : GetOnlySingleNode(state,
293 1 : Alphas(5),
294 : ErrorsFound,
295 : DataLoopNode::ConnectionObjectType::AirTerminalSingleDuctConstantVolumeFourPipeInduction,
296 1 : Alphas(1),
297 : DataLoopNode::NodeFluidType::Air,
298 : DataLoopNode::ConnectionType::Outlet,
299 : NodeInputManager::CompFluidStream::Primary,
300 : DataLoopNode::ObjectIsParent,
301 1 : cAlphaFields(5));
302 :
303 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoilType = Alphas(6); // type (key) of heating coil
304 1 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoilType, "Coil:Heating:Water")) {
305 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HeatingCoilType = DataPlant::PlantEquipmentType::CoilWaterSimpleHeating;
306 : }
307 :
308 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil = Alphas(7); // name of heating coil object
309 1 : bool IsNotOK = false;
310 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWControlNode = WaterCoils::GetCoilWaterInletNode(
311 1 : state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoilType, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil, IsNotOK);
312 1 : if (IsNotOK) {
313 0 : ShowContinueError(state, format("In {} = {}", CurrentModuleObject, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
314 0 : ShowContinueError(state, "..Only Coil:Heating:Water is allowed.");
315 0 : ErrorsFound = true;
316 : }
317 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow = Numbers(3);
318 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinVolHotWaterFlow = Numbers(4);
319 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HotControlOffset = Numbers(5);
320 :
321 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType = Alphas(8); // type (key) of cooling coil
322 :
323 1 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType, "Coil:Cooling:Water")) {
324 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CoolingCoilType = DataPlant::PlantEquipmentType::CoilWaterCooling;
325 0 : } else if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType, "Coil:Cooling:Water:DetailedGeometry")) {
326 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CoolingCoilType = DataPlant::PlantEquipmentType::CoilWaterDetailedFlatCooling;
327 : }
328 :
329 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil = Alphas(9); // name of cooling coil object
330 1 : IsNotOK = false;
331 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWControlNode = WaterCoils::GetCoilWaterInletNode(
332 1 : state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil, IsNotOK);
333 1 : if (IsNotOK) {
334 0 : ShowContinueError(state, format("In {} = {}", CurrentModuleObject, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
335 0 : ShowContinueError(state, "..Only Coil:Cooling:Water or Coil:Cooling:Water:DetailedGeometry is allowed.");
336 0 : ErrorsFound = true;
337 : }
338 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow = Numbers(6);
339 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinVolColdWaterFlow = Numbers(7);
340 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).ColdControlOffset = Numbers(8);
341 :
342 : // Get the Zone Mixer name and check that it is OK
343 1 : bool errFlag = false;
344 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MixerName = Alphas(10);
345 1 : MixerComponent::GetZoneMixerIndex(state,
346 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MixerName,
347 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Mixer_Num,
348 : errFlag,
349 : CurrentModuleObject);
350 1 : if (errFlag) {
351 0 : ShowContinueError(state, format("...specified in {} = {}", CurrentModuleObject, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
352 0 : ErrorsFound = true;
353 : }
354 :
355 : // Add heating coil to component sets array
356 2 : BranchNodeConnections::SetUpCompSets(state,
357 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
358 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
359 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoilType,
360 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil,
361 1 : Alphas(4),
362 : "UNDEFINED");
363 : // Add cooling coil to component sets array
364 2 : BranchNodeConnections::SetUpCompSets(state,
365 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
366 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
367 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType,
368 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil,
369 : "UNDEFINED",
370 : "UNDEFINED");
371 :
372 : // Register component set data
373 2 : BranchNodeConnections::TestCompSet(state,
374 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
375 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
376 1 : state.dataLoopNodes->NodeID(state.dataHVACSingleDuctInduc->IndUnit(IUNum).PriAirInNode),
377 1 : state.dataLoopNodes->NodeID(state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode),
378 : "Air Nodes");
379 :
380 2 : for (int ADUNum = 1; ADUNum <= (int)state.dataDefineEquipment->AirDistUnit.size(); ++ADUNum) {
381 1 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode == state.dataDefineEquipment->AirDistUnit(ADUNum).OutletNodeNum) {
382 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).ADUNum = ADUNum;
383 : }
384 : }
385 : // one assumes if there isn't one assigned, it's an error?
386 1 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).ADUNum == 0) {
387 0 : ShowSevereError(state,
388 0 : format("{}No matching Air Distribution Unit, for Unit = [{},{}].",
389 : RoutineName,
390 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
391 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
392 0 : ShowContinueError(
393 : state,
394 0 : format("...should have outlet node={}", state.dataLoopNodes->NodeID(state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode)));
395 0 : ErrorsFound = true;
396 : } else {
397 : // Fill the Zone Equipment data with the supply air inlet node number of this unit.
398 1 : bool AirNodeFound = false;
399 2 : for (int CtrlZone = 1; CtrlZone <= state.dataGlobal->NumOfZones; ++CtrlZone) {
400 1 : auto &zoneEquipConfig = state.dataZoneEquip->ZoneEquipConfig(CtrlZone);
401 :
402 1 : if (!zoneEquipConfig.IsControlled) {
403 0 : continue;
404 : }
405 1 : for (int SupAirIn = 1; SupAirIn <= zoneEquipConfig.NumInletNodes; ++SupAirIn) {
406 1 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode == zoneEquipConfig.InletNode(SupAirIn)) {
407 1 : if (zoneEquipConfig.AirDistUnitCool(SupAirIn).OutNode > 0) {
408 0 : ShowSevereError(state, "Error in connecting a terminal unit to a zone");
409 0 : ShowContinueError(state,
410 0 : format("{} already connects to another zone",
411 0 : state.dataLoopNodes->NodeID(state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode)));
412 0 : ShowContinueError(state,
413 0 : format("Occurs for terminal unit {} = {}",
414 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
415 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
416 0 : ShowContinueError(state, "Check terminal unit node names for errors");
417 0 : ErrorsFound = true;
418 : } else {
419 1 : zoneEquipConfig.AirDistUnitCool(SupAirIn).InNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).PriAirInNode;
420 1 : zoneEquipConfig.AirDistUnitCool(SupAirIn).OutNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode;
421 1 : state.dataDefineEquipment->AirDistUnit(state.dataHVACSingleDuctInduc->IndUnit(IUNum).ADUNum).TermUnitSizingNum =
422 1 : zoneEquipConfig.AirDistUnitCool(SupAirIn).TermUnitSizingIndex;
423 1 : state.dataDefineEquipment->AirDistUnit(state.dataHVACSingleDuctInduc->IndUnit(IUNum).ADUNum).ZoneEqNum = CtrlZone;
424 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CtrlZoneNum = CtrlZone;
425 : }
426 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CtrlZoneInNodeIndex = SupAirIn;
427 1 : AirNodeFound = true;
428 1 : break;
429 : }
430 : }
431 : }
432 1 : if (!AirNodeFound) {
433 0 : ShowSevereError(
434 : state,
435 0 : format("The outlet air node from the {} = {}", CurrentModuleObject, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
436 0 : ShowContinueError(state, format("did not have a matching Zone Equipment Inlet Node, Node ={}", Alphas(3)));
437 0 : ErrorsFound = true;
438 : }
439 : }
440 : // report variable for all single duct air terminals
441 2 : SetupOutputVariable(state,
442 : "Zone Air Terminal Outdoor Air Volume Flow Rate",
443 : Constant::Units::m3_s,
444 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutdoorAirFlowRate,
445 : OutputProcessor::TimeStepType::System,
446 : OutputProcessor::StoreType::Average,
447 1 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name);
448 : }
449 :
450 1 : Alphas.deallocate();
451 1 : cAlphaFields.deallocate();
452 1 : cNumericFields.deallocate();
453 1 : Numbers.deallocate();
454 1 : lAlphaBlanks.deallocate();
455 1 : lNumericBlanks.deallocate();
456 1 : if (ErrorsFound) {
457 0 : ShowFatalError(state, format("{}Errors found in getting input. Preceding conditions cause termination.", RoutineName));
458 : }
459 1 : }
460 :
461 0 : void InitIndUnit(EnergyPlusData &state,
462 : int const IUNum, // number of the current induction unit being simulated
463 : bool const FirstHVACIteration // TRUE if first air loop solution this HVAC step
464 : )
465 : {
466 :
467 : // SUBROUTINE INFORMATION:
468 : // AUTHOR Fred Buhl
469 : // DATE WRITTEN June 21 2004
470 :
471 : // PURPOSE OF THIS SUBROUTINE:
472 : // This subroutine is for initialization of the passive induction terminal boxes
473 :
474 : // METHODOLOGY EMPLOYED:
475 : // Uses the status flags to trigger initializations.
476 :
477 : // SUBROUTINE PARAMETER DEFINITIONS:
478 : static constexpr std::string_view RoutineName("InitIndUnit");
479 :
480 : // SUBROUTINE LOCAL VARIABLE DECLARATIONS:
481 : int PriNode; // primary air inlet node number
482 : int SecNode; // secondary air inlet node number
483 : Real64 IndRat; // unit induction ratio
484 : Real64 RhoAir; // air density at outside pressure and standard temperature and humidity
485 : Real64 rho; // local fluid density
486 :
487 0 : auto &ZoneEquipmentListChecked = state.dataHVACSingleDuctInduc->ZoneEquipmentListChecked;
488 :
489 : // Do the one time initializations
490 0 : if (state.dataHVACSingleDuctInduc->MyOneTimeFlag) {
491 :
492 0 : state.dataHVACSingleDuctInduc->MyEnvrnFlag.allocate(state.dataHVACSingleDuctInduc->NumIndUnits);
493 0 : state.dataHVACSingleDuctInduc->MySizeFlag.allocate(state.dataHVACSingleDuctInduc->NumIndUnits);
494 0 : state.dataHVACSingleDuctInduc->MyPlantScanFlag.allocate(state.dataHVACSingleDuctInduc->NumIndUnits);
495 0 : state.dataHVACSingleDuctInduc->MyAirDistInitFlag.allocate(state.dataHVACSingleDuctInduc->NumIndUnits);
496 0 : state.dataHVACSingleDuctInduc->MyEnvrnFlag = true;
497 0 : state.dataHVACSingleDuctInduc->MySizeFlag = true;
498 0 : state.dataHVACSingleDuctInduc->MyPlantScanFlag = true;
499 0 : state.dataHVACSingleDuctInduc->MyAirDistInitFlag = true;
500 0 : state.dataHVACSingleDuctInduc->MyOneTimeFlag = false;
501 : }
502 :
503 0 : if (state.dataHVACSingleDuctInduc->MyPlantScanFlag(IUNum) && allocated(state.dataPlnt->PlantLoop)) {
504 0 : bool errFlag = false;
505 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).HeatingCoilType == DataPlant::PlantEquipmentType::CoilWaterSimpleHeating) {
506 0 : errFlag = false;
507 0 : PlantUtilities::ScanPlantLoopsForObject(state,
508 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil,
509 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HeatingCoilType,
510 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc,
511 : errFlag,
512 : _,
513 : _,
514 : _,
515 : _,
516 : _);
517 : }
518 0 : if (errFlag) {
519 0 : ShowContinueError(state,
520 0 : format("Reference Unit=\"{}\", type={}",
521 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
522 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType));
523 : }
524 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).CoolingCoilType == DataPlant::PlantEquipmentType::CoilWaterCooling ||
525 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CoolingCoilType == DataPlant::PlantEquipmentType::CoilWaterDetailedFlatCooling) {
526 0 : errFlag = false;
527 0 : PlantUtilities::ScanPlantLoopsForObject(state,
528 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil,
529 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CoolingCoilType,
530 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc,
531 : errFlag,
532 : _,
533 : _,
534 : _,
535 : _,
536 : _);
537 : }
538 0 : if (errFlag) {
539 0 : ShowContinueError(state,
540 0 : format("Reference Unit=\"{}\", type={}",
541 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
542 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType));
543 0 : ShowFatalError(state, "InitIndUnit: Program terminated for previous conditions.");
544 : }
545 0 : state.dataHVACSingleDuctInduc->MyPlantScanFlag(IUNum) = false;
546 0 : } else if (state.dataHVACSingleDuctInduc->MyPlantScanFlag(IUNum) && !state.dataGlobal->AnyPlantInModel) {
547 0 : state.dataHVACSingleDuctInduc->MyPlantScanFlag(IUNum) = false;
548 : }
549 :
550 0 : if (state.dataHVACSingleDuctInduc->MyAirDistInitFlag(IUNum)) {
551 : // save the induction ratio in the term unit sizing array for use in the system sizing calculation
552 0 : if (state.dataSize->CurTermUnitSizingNum > 0) {
553 0 : state.dataSize->TermUnitSizing(state.dataSize->CurTermUnitSizingNum).InducRat =
554 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio;
555 : }
556 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).AirLoopNum == 0) {
557 0 : if ((state.dataHVACSingleDuctInduc->IndUnit(IUNum).CtrlZoneNum > 0) &&
558 0 : (state.dataHVACSingleDuctInduc->IndUnit(IUNum).CtrlZoneInNodeIndex > 0)) {
559 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).AirLoopNum =
560 0 : state.dataZoneEquip->ZoneEquipConfig(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CtrlZoneNum)
561 0 : .InletNodeAirLoopNum(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CtrlZoneInNodeIndex);
562 0 : state.dataDefineEquipment->AirDistUnit(state.dataHVACSingleDuctInduc->IndUnit(IUNum).ADUNum).AirLoopNum =
563 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).AirLoopNum;
564 : }
565 : } else {
566 0 : state.dataHVACSingleDuctInduc->MyAirDistInitFlag(IUNum) = false;
567 : }
568 : }
569 0 : if (!ZoneEquipmentListChecked && state.dataZoneEquip->ZoneEquipInputsFilled) {
570 0 : ZoneEquipmentListChecked = true;
571 : // Check to see if there is a Air Distribution Unit on the Zone Equipment List
572 0 : for (int Loop = 1; Loop <= state.dataHVACSingleDuctInduc->NumIndUnits; ++Loop) {
573 0 : if (state.dataHVACSingleDuctInduc->IndUnit(Loop).ADUNum == 0) {
574 0 : continue;
575 : }
576 0 : if (DataZoneEquipment::CheckZoneEquipmentList(
577 : state,
578 : "ZONEHVAC:AIRDISTRIBUTIONUNIT",
579 0 : state.dataDefineEquipment->AirDistUnit(state.dataHVACSingleDuctInduc->IndUnit(Loop).ADUNum).Name)) {
580 0 : continue;
581 : }
582 0 : ShowSevereError(state,
583 0 : format("InitIndUnit: ADU=[Air Distribution Unit,{}] is not on any ZoneHVAC:EquipmentList.",
584 0 : state.dataDefineEquipment->AirDistUnit(state.dataHVACSingleDuctInduc->IndUnit(Loop).ADUNum).Name));
585 0 : ShowContinueError(state,
586 0 : format("...Unit=[{},{}] will not be simulated.",
587 0 : state.dataHVACSingleDuctInduc->IndUnit(Loop).UnitType,
588 0 : state.dataHVACSingleDuctInduc->IndUnit(Loop).Name));
589 : }
590 : }
591 :
592 0 : if (!state.dataGlobal->SysSizingCalc && state.dataHVACSingleDuctInduc->MySizeFlag(IUNum)) {
593 :
594 0 : SizeIndUnit(state, IUNum);
595 0 : state.dataHVACSingleDuctInduc->MySizeFlag(IUNum) = false;
596 : }
597 :
598 : // Do the Begin Environment initializations
599 0 : if (state.dataGlobal->BeginEnvrnFlag && state.dataHVACSingleDuctInduc->MyEnvrnFlag(IUNum)) {
600 0 : RhoAir = state.dataEnvrn->StdRhoAir;
601 0 : PriNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).PriAirInNode;
602 0 : SecNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).SecAirInNode;
603 0 : int OutletNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode;
604 0 : IndRat = state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio;
605 : // set the mass flow rates from the input volume flow rates
606 0 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType, "AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction")) {
607 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirMassFlow =
608 0 : RhoAir * state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow;
609 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxPriAirMassFlow =
610 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirMassFlow / (1.0 + IndRat);
611 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxSecAirMassFlow =
612 0 : IndRat * state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirMassFlow / (1.0 + IndRat);
613 0 : state.dataLoopNodes->Node(PriNode).MassFlowRateMax = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxPriAirMassFlow;
614 0 : state.dataLoopNodes->Node(PriNode).MassFlowRateMin = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxPriAirMassFlow;
615 0 : state.dataLoopNodes->Node(SecNode).MassFlowRateMax = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxSecAirMassFlow;
616 0 : state.dataLoopNodes->Node(SecNode).MassFlowRateMin = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxSecAirMassFlow;
617 0 : state.dataLoopNodes->Node(OutletNode).MassFlowRateMax = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirMassFlow;
618 : }
619 :
620 0 : int HotConNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWControlNode;
621 0 : if (HotConNode > 0 && !state.dataHVACSingleDuctInduc->MyPlantScanFlag(IUNum)) {
622 :
623 0 : rho = state.dataPlnt->PlantLoop(state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc.loopNum)
624 0 : .glycol->getDensity(state, Constant::HWInitConvTemp, RoutineName);
625 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxHotWaterFlow =
626 0 : rho * state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow;
627 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinHotWaterFlow =
628 0 : rho * state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinVolHotWaterFlow;
629 : // get component outlet node from plant structure
630 0 : int HWOutletNode = DataPlant::CompData::getPlantComponent(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc).NodeNumOut;
631 0 : PlantUtilities::InitComponentNodes(state,
632 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinHotWaterFlow,
633 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxHotWaterFlow,
634 : HotConNode,
635 : HWOutletNode);
636 : }
637 :
638 0 : int ColdConNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWControlNode;
639 0 : if (ColdConNode > 0) {
640 0 : rho = state.dataPlnt->PlantLoop(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc.loopNum)
641 0 : .glycol->getDensity(state, Constant::CWInitConvTemp, RoutineName);
642 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxColdWaterFlow =
643 0 : rho * state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow;
644 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinColdWaterFlow =
645 0 : rho * state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinVolColdWaterFlow;
646 :
647 0 : int CWOutletNode = DataPlant::CompData::getPlantComponent(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc).NodeNumOut;
648 0 : PlantUtilities::InitComponentNodes(state,
649 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinColdWaterFlow,
650 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxColdWaterFlow,
651 : ColdConNode,
652 : CWOutletNode);
653 : }
654 :
655 0 : state.dataHVACSingleDuctInduc->MyEnvrnFlag(IUNum) = false;
656 : } // end one time inits
657 :
658 0 : if (!state.dataGlobal->BeginEnvrnFlag) {
659 0 : state.dataHVACSingleDuctInduc->MyEnvrnFlag(IUNum) = true;
660 : }
661 :
662 0 : PriNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).PriAirInNode;
663 0 : SecNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).SecAirInNode;
664 :
665 : // Do the start of HVAC time step initializations
666 0 : if (FirstHVACIteration) {
667 : // check for upstream zero flow. If nonzero and schedule ON, set primary flow to max
668 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).availSched->getCurrentVal() > 0.0 &&
669 0 : state.dataLoopNodes->Node(PriNode).MassFlowRate > 0.0) {
670 0 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
671 : "AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction")) {
672 0 : state.dataLoopNodes->Node(PriNode).MassFlowRate = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxPriAirMassFlow;
673 0 : state.dataLoopNodes->Node(SecNode).MassFlowRate = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxSecAirMassFlow;
674 : }
675 : } else {
676 0 : state.dataLoopNodes->Node(PriNode).MassFlowRate = 0.0;
677 0 : state.dataLoopNodes->Node(SecNode).MassFlowRate = 0.0;
678 : }
679 : // reset the max and min avail flows
680 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).availSched->getCurrentVal() > 0.0 &&
681 0 : state.dataLoopNodes->Node(PriNode).MassFlowRateMaxAvail > 0.0) {
682 0 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
683 : "AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction")) {
684 0 : state.dataLoopNodes->Node(PriNode).MassFlowRateMaxAvail = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxPriAirMassFlow;
685 0 : state.dataLoopNodes->Node(PriNode).MassFlowRateMinAvail = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxPriAirMassFlow;
686 0 : state.dataLoopNodes->Node(SecNode).MassFlowRateMaxAvail = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxSecAirMassFlow;
687 0 : state.dataLoopNodes->Node(SecNode).MassFlowRateMinAvail = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxSecAirMassFlow;
688 : }
689 : } else {
690 0 : state.dataLoopNodes->Node(PriNode).MassFlowRateMaxAvail = 0.0;
691 0 : state.dataLoopNodes->Node(PriNode).MassFlowRateMinAvail = 0.0;
692 0 : state.dataLoopNodes->Node(SecNode).MassFlowRateMaxAvail = 0.0;
693 0 : state.dataLoopNodes->Node(SecNode).MassFlowRateMinAvail = 0.0;
694 : }
695 : }
696 0 : }
697 :
698 0 : void SizeIndUnit(EnergyPlusData &state, int const IUNum)
699 : {
700 :
701 : // SUBROUTINE INFORMATION:
702 : // AUTHOR Fred Buhl
703 : // DATE WRITTEN June 22 2004
704 : // MODIFIED August 2013 Daeho Kang, add component sizing table entries
705 :
706 : // PURPOSE OF THIS SUBROUTINE:
707 : // This subroutine is for sizing induction terminal units for which flow rates have not been
708 : // specified in the input
709 :
710 : // METHODOLOGY EMPLOYED:
711 : // Accesses zone sizing array for air flow rates and zone and plant sizing arrays to
712 : // calculate coil water flow rates.
713 :
714 : // SUBROUTINE PARAMETER DEFINITIONS:
715 : static constexpr std::string_view RoutineName("SizeIndUnit");
716 :
717 : // SUBROUTINE LOCAL VARIABLE DECLARATIONS:
718 : Real64 DesCoilLoad;
719 : Real64 Cp; // local fluid specific heat
720 : Real64 rho; // local fluid density
721 :
722 0 : Real64 DesPriVolFlow = 0.0;
723 0 : Real64 CpAir = 0.0;
724 0 : Real64 RhoAir = state.dataEnvrn->StdRhoAir;
725 0 : bool ErrorsFound = false;
726 0 : bool IsAutoSize = false;
727 0 : Real64 MaxTotAirVolFlowDes = 0.0; // Design size maximum air volume flow for reporting
728 0 : Real64 MaxTotAirVolFlowUser = 0.0; // User hard-sized maximum air volume flow for reporting
729 0 : Real64 MaxVolHotWaterFlowDes = 0.0; // Design size maximum hot water flow for reporting
730 0 : Real64 MaxVolHotWaterFlowUser = 0.0; // User hard-sized maximum hot water flow for reporting
731 0 : Real64 MaxVolColdWaterFlowDes = 0.0; // Design size maximum cold water flow for reporting
732 0 : Real64 MaxVolColdWaterFlowUser = 0.0; // User hard-sized maximum cold water flow for reporting
733 :
734 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow == DataSizing::AutoSize) {
735 0 : IsAutoSize = true;
736 : }
737 :
738 0 : if (state.dataSize->CurZoneEqNum > 0) {
739 0 : if (!IsAutoSize && !state.dataSize->ZoneSizingRunDone) { // simulation continue
740 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow > 0.0) {
741 0 : BaseSizer::reportSizerOutput(state,
742 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
743 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
744 : "User-Specified Maximum Total Air Flow Rate [m3/s]",
745 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow);
746 : }
747 : } else {
748 0 : CheckZoneSizing(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name);
749 0 : if (state.dataSize->CurTermUnitSizingNum > 0) {
750 0 : MaxTotAirVolFlowDes = max(state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesCoolVolFlow,
751 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow);
752 : } else {
753 0 : MaxTotAirVolFlowDes = 0.0;
754 : }
755 0 : if (MaxTotAirVolFlowDes < HVAC::SmallAirVolFlow) {
756 0 : MaxTotAirVolFlowDes = 0.0;
757 : }
758 0 : if (IsAutoSize) {
759 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow = MaxTotAirVolFlowDes;
760 0 : BaseSizer::reportSizerOutput(state,
761 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
762 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
763 : "Design Size Maximum Total Air Flow Rate [m3/s]",
764 : MaxTotAirVolFlowDes);
765 : } else {
766 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow > 0.0 && MaxTotAirVolFlowDes > 0.0) {
767 0 : MaxTotAirVolFlowUser = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow;
768 0 : BaseSizer::reportSizerOutput(state,
769 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
770 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
771 : "Design Size Maximum Total Air Flow Rate [m3/s]",
772 : MaxTotAirVolFlowDes,
773 : "User-Specified Maximum Total Air Flow Rate [m3/s]",
774 : MaxTotAirVolFlowUser);
775 0 : if (state.dataGlobal->DisplayExtraWarnings) {
776 0 : if ((std::abs(MaxTotAirVolFlowDes - MaxTotAirVolFlowUser) / MaxTotAirVolFlowUser) >
777 0 : state.dataSize->AutoVsHardSizingThreshold) {
778 0 : ShowMessage(state,
779 0 : format("SizeHVACSingleDuctInduction: Potential issue with equipment sizing for {} = \"{}\".",
780 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
781 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
782 0 : ShowContinueError(state, format("User-Specified Maximum Total Air Flow Rate of {:.5R} [m3/s]", MaxTotAirVolFlowUser));
783 0 : ShowContinueError(
784 0 : state, format("differs from Design Size Maximum Total Air Flow Rate of {:.5R} [m3/s]", MaxTotAirVolFlowDes));
785 0 : ShowContinueError(state, "This may, or may not, indicate mismatched component sizes.");
786 0 : ShowContinueError(state, "Verify that the value entered is intended and is consistent with other components.");
787 : }
788 : }
789 : }
790 : }
791 : }
792 : }
793 :
794 0 : IsAutoSize = false;
795 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow == DataSizing::AutoSize) {
796 0 : IsAutoSize = true;
797 : }
798 0 : if ((state.dataSize->CurZoneEqNum > 0) && (state.dataSize->CurTermUnitSizingNum > 0)) {
799 0 : if (!IsAutoSize && !state.dataSize->ZoneSizingRunDone) { // simulation continue
800 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow > 0.0) {
801 0 : BaseSizer::reportSizerOutput(state,
802 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
803 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
804 : "User-Specified Maximum Hot Water Flow Rate [m3/s]",
805 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow);
806 : }
807 : } else {
808 0 : CheckZoneSizing(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name);
809 :
810 0 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoilType, "Coil:Heating:Water")) {
811 :
812 0 : int CoilWaterInletNode = WaterCoils::GetCoilWaterInletNode(
813 0 : state, "Coil:Heating:Water", state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil, ErrorsFound);
814 0 : int CoilWaterOutletNode = WaterCoils::GetCoilWaterOutletNode(
815 0 : state, "Coil:Heating:Water", state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil, ErrorsFound);
816 0 : if (IsAutoSize) {
817 0 : int PltSizHeatNum = PlantUtilities::MyPlantSizingIndex(state,
818 : "Coil:Heating:Water",
819 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil,
820 : CoilWaterInletNode,
821 : CoilWaterOutletNode,
822 : ErrorsFound);
823 0 : if (PltSizHeatNum > 0) {
824 :
825 0 : if (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatMassFlow >=
826 : HVAC::SmallAirVolFlow) {
827 0 : DesPriVolFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow /
828 0 : (1.0 + state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio);
829 0 : CpAir = Psychrometrics::PsyCpAirFnW(
830 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).HeatDesHumRat);
831 : // the design heating coil load is the zone load minus whatever the central system does. Note that
832 : // DesHeatCoilInTempTU is really the primary air inlet temperature for the unit.
833 0 : if (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).ZoneTempAtHeatPeak > 0.0) {
834 0 : DesCoilLoad =
835 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).NonAirSysDesHeatLoad -
836 0 : CpAir * RhoAir * DesPriVolFlow *
837 0 : (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatCoilInTempTU -
838 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).ZoneTempAtHeatPeak);
839 : } else {
840 0 : DesCoilLoad = CpAir * RhoAir * DesPriVolFlow *
841 0 : (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).ZoneSizThermSetPtLo -
842 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatCoilInTempTU);
843 : }
844 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).DesHeatingLoad = DesCoilLoad;
845 0 : Cp = state.dataPlnt->PlantLoop(state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc.loopNum)
846 0 : .glycol->getSpecificHeat(state, Constant::HWInitConvTemp, RoutineName);
847 :
848 0 : rho = state.dataPlnt->PlantLoop(state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc.loopNum)
849 0 : .glycol->getDensity(state, Constant::HWInitConvTemp, RoutineName);
850 :
851 0 : MaxVolHotWaterFlowDes = DesCoilLoad / (state.dataSize->PlantSizData(PltSizHeatNum).DeltaT * Cp * rho);
852 0 : MaxVolHotWaterFlowDes = max(MaxVolHotWaterFlowDes, 0.0);
853 : } else {
854 0 : MaxVolHotWaterFlowDes = 0.0;
855 : }
856 : } else {
857 0 : ShowSevereError(state, "Autosizing of water flow requires a heating loop Sizing:Plant object");
858 0 : ShowContinueError(state,
859 0 : format("Occurs in{} Object={}",
860 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
861 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
862 0 : ErrorsFound = true;
863 : }
864 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow = MaxVolHotWaterFlowDes;
865 0 : BaseSizer::reportSizerOutput(state,
866 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
867 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
868 : "Design Size Maximum Hot Water Flow Rate [m3/s]",
869 : MaxVolHotWaterFlowDes);
870 0 : BaseSizer::reportSizerOutput(
871 : state,
872 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
873 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
874 : "Design Size Inlet Air Temperature [C]",
875 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatCoilInTempTU);
876 0 : BaseSizer::reportSizerOutput(
877 : state,
878 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
879 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
880 : "Design Size Inlet Air Humidity Ratio [kgWater/kgDryAir]",
881 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatCoilInHumRatTU);
882 : } else {
883 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow > 0.0 && MaxVolHotWaterFlowDes > 0.0) {
884 0 : MaxVolHotWaterFlowUser = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow;
885 0 : BaseSizer::reportSizerOutput(state,
886 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
887 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
888 : "Design Size Maximum Hot Water Flow Rate [m3/s]",
889 : MaxVolHotWaterFlowDes,
890 : "User-Specified Maximum Hot Water Flow Rate [m3/s]",
891 : MaxVolHotWaterFlowUser);
892 0 : if (state.dataGlobal->DisplayExtraWarnings) {
893 0 : if ((std::abs(MaxVolHotWaterFlowDes - MaxVolHotWaterFlowUser) / MaxVolHotWaterFlowUser) >
894 0 : state.dataSize->AutoVsHardSizingThreshold) {
895 0 : ShowMessage(state,
896 0 : format("SizeHVACSingleDuctInduction: Potential issue with equipment sizing for {} = \"{}\".",
897 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
898 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
899 0 : ShowContinueError(state,
900 0 : format("User-Specified Maximum Hot Water Flow Rate of {:.5R} [m3/s]", MaxVolHotWaterFlowUser));
901 0 : ShowContinueError(
902 : state,
903 0 : format("differs from Design Size Maximum Hot Water Flow Rate of {:.5R} [m3/s]", MaxVolHotWaterFlowDes));
904 0 : ShowContinueError(state, "This may, or may not, indicate mismatched component sizes.");
905 0 : ShowContinueError(state, "Verify that the value entered is intended and is consistent with other components.");
906 : }
907 : }
908 : }
909 : }
910 : } else {
911 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow = 0.0;
912 : }
913 : }
914 : }
915 :
916 0 : IsAutoSize = false;
917 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow == DataSizing::AutoSize) {
918 0 : IsAutoSize = true;
919 : }
920 0 : if ((state.dataSize->CurZoneEqNum > 0) && (state.dataSize->CurTermUnitSizingNum > 0)) {
921 0 : if (!IsAutoSize && !state.dataSize->ZoneSizingRunDone) { // simulation continue
922 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow > 0.0) {
923 0 : BaseSizer::reportSizerOutput(state,
924 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
925 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
926 : "User-Specified Maximum Cold Water Flow Rate [m3/s]",
927 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow);
928 : }
929 : } else {
930 0 : CheckZoneSizing(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name);
931 :
932 0 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType, "Coil:Cooling:Water") ||
933 0 : Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType, "Coil:Cooling:Water:DetailedGeometry")) {
934 :
935 0 : int CoilWaterInletNode = WaterCoils::GetCoilWaterInletNode(state,
936 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType,
937 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil,
938 : ErrorsFound);
939 0 : int CoilWaterOutletNode = WaterCoils::GetCoilWaterOutletNode(state,
940 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType,
941 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil,
942 : ErrorsFound);
943 0 : if (IsAutoSize) {
944 0 : int PltSizCoolNum = PlantUtilities::MyPlantSizingIndex(state,
945 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType,
946 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil,
947 : CoilWaterInletNode,
948 : CoilWaterOutletNode,
949 : ErrorsFound);
950 0 : if (PltSizCoolNum > 0) {
951 :
952 0 : if (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesCoolMassFlow >=
953 : HVAC::SmallAirVolFlow) {
954 0 : DesPriVolFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow /
955 0 : (1.0 + state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio);
956 0 : CpAir = Psychrometrics::PsyCpAirFnW(
957 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).CoolDesHumRat);
958 : // the design cooling coil load is the zone load minus whatever the central system does. Note that
959 : // DesCoolCoilInTempTU is really the primary air inlet temperature for the unit.
960 0 : if (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).ZoneTempAtCoolPeak > 0.0) {
961 0 : DesCoilLoad =
962 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).NonAirSysDesCoolLoad -
963 0 : CpAir * RhoAir * DesPriVolFlow *
964 0 : (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).ZoneTempAtCoolPeak -
965 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesCoolCoilInTempTU);
966 : } else {
967 0 : DesCoilLoad = CpAir * RhoAir * DesPriVolFlow *
968 0 : (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesCoolCoilInTempTU -
969 0 : state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).ZoneSizThermSetPtHi);
970 : }
971 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).DesCoolingLoad = DesCoilLoad;
972 0 : Cp = state.dataPlnt->PlantLoop(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc.loopNum)
973 0 : .glycol->getSpecificHeat(state, 5.0, RoutineName);
974 :
975 0 : rho = state.dataPlnt->PlantLoop(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc.loopNum)
976 0 : .glycol->getDensity(state, 5.0, RoutineName);
977 :
978 0 : MaxVolColdWaterFlowDes = DesCoilLoad / (state.dataSize->PlantSizData(PltSizCoolNum).DeltaT * Cp * rho);
979 0 : MaxVolColdWaterFlowDes = max(MaxVolColdWaterFlowDes, 0.0);
980 : } else {
981 0 : MaxVolColdWaterFlowDes = 0.0;
982 : }
983 : } else {
984 0 : ShowSevereError(state, "Autosizing of water flow requires a cooling loop Sizing:Plant object");
985 0 : ShowContinueError(state,
986 0 : format("Occurs in{} Object={}",
987 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
988 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
989 0 : ErrorsFound = true;
990 : }
991 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow = MaxVolColdWaterFlowDes;
992 0 : BaseSizer::reportSizerOutput(state,
993 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
994 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
995 : "Design Size Maximum Cold Water Flow Rate [m3/s]",
996 : MaxVolColdWaterFlowDes);
997 : } else {
998 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow > 0.0 && MaxVolColdWaterFlowDes > 0.0) {
999 0 : MaxVolColdWaterFlowUser = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow;
1000 0 : BaseSizer::reportSizerOutput(state,
1001 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1002 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name,
1003 : "Design Size Maximum Cold Water Flow Rate [m3/s]",
1004 : MaxVolColdWaterFlowDes,
1005 : "User-Specified Maximum Cold Water Flow Rate [m3/s]",
1006 : MaxVolColdWaterFlowUser);
1007 0 : if (state.dataGlobal->DisplayExtraWarnings) {
1008 0 : if ((std::abs(MaxVolColdWaterFlowDes - MaxVolColdWaterFlowUser) / MaxVolColdWaterFlowUser) >
1009 0 : state.dataSize->AutoVsHardSizingThreshold) {
1010 0 : ShowMessage(state,
1011 0 : format("SizeHVACSingleDuctInduction: Potential issue with equipment sizing for {} = \"{}\".",
1012 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1013 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
1014 0 : ShowContinueError(
1015 0 : state, format("User-Specified Maximum Cold Water Flow Rate of {:.5R} [m3/s]", MaxVolColdWaterFlowUser));
1016 0 : ShowContinueError(
1017 : state,
1018 0 : format("differs from Design Size Maximum Cold Water Flow Rate of {:.5R} [m3/s]", MaxVolColdWaterFlowDes));
1019 0 : ShowContinueError(state, "This may, or may not, indicate mismatched component sizes.");
1020 0 : ShowContinueError(state, "Verify that the value entered is intended and is consistent with other components.");
1021 : }
1022 : }
1023 : }
1024 : }
1025 : } else {
1026 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow = 0.0;
1027 : }
1028 : }
1029 : }
1030 :
1031 0 : if (state.dataSize->CurTermUnitSizingNum > 0) {
1032 0 : auto &termUnitSizing = state.dataSize->TermUnitSizing(state.dataSize->CurTermUnitSizingNum);
1033 :
1034 : // note we save the induced air flow for use by the hw and cw coil sizing routines
1035 0 : termUnitSizing.AirVolFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirVolFlow *
1036 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio /
1037 0 : (1.0 + state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio);
1038 : // save the max hot and cold water flows for use in coil sizing
1039 0 : termUnitSizing.MaxHWVolFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolHotWaterFlow;
1040 0 : termUnitSizing.MaxCWVolFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxVolColdWaterFlow;
1041 : // save the design load used for reporting
1042 0 : termUnitSizing.DesCoolingLoad = state.dataHVACSingleDuctInduc->IndUnit(IUNum).DesCoolingLoad;
1043 0 : termUnitSizing.DesHeatingLoad = state.dataHVACSingleDuctInduc->IndUnit(IUNum).DesHeatingLoad;
1044 : // save the induction ratio for use in subsequent sizing calcs
1045 0 : termUnitSizing.InducRat = state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio;
1046 0 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoilType, "Coil:Heating:Water")) {
1047 0 : WaterCoils::SetCoilDesFlow(state,
1048 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoilType,
1049 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil,
1050 : termUnitSizing.AirVolFlow,
1051 : ErrorsFound);
1052 : }
1053 0 : if (Util::SameString(state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType, "Coil:Cooling:Water:DetailedGeometry")) {
1054 0 : WaterCoils::SetCoilDesFlow(state,
1055 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoilType,
1056 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil,
1057 : termUnitSizing.AirVolFlow,
1058 : ErrorsFound);
1059 : }
1060 : }
1061 0 : }
1062 :
1063 0 : void SimFourPipeIndUnit(EnergyPlusData &state,
1064 : int const IUNum, // number of the current unit being simulated
1065 : int const ZoneNum, // number of zone being served
1066 : int const ZoneNodeNum, // zone node number
1067 : bool const FirstHVACIteration // TRUE if 1st HVAC simulation of system timestep
1068 : )
1069 : {
1070 :
1071 : // SUBROUTINE INFORMATION:
1072 : // AUTHOR Fred Buhl
1073 : // DATE WRITTEN June 23 2004
1074 :
1075 : // PURPOSE OF THIS SUBROUTINE:
1076 : // Simulate a 4 pipe induction unit; adjust its heating or cooling
1077 : // coil outputs to match the zone load.
1078 :
1079 : // METHODOLOGY EMPLOYED:
1080 : // (1) From the zone load and the primary air inlet conditions calculate the coil load
1081 : // in the secondary air stream
1082 : // (2) If there is a cooling coil load, set the heating coil off and control the cooling
1083 : // coil to meet the coil load
1084 : // (3) If there is a heating coil load, control the heating coil to meet the load and keep
1085 : // the cooling coil off.
1086 :
1087 : // SUBROUTINE PARAMETER DEFINITIONS:
1088 0 : int constexpr SolveMaxIter(50);
1089 :
1090 : // SUBROUTINE LOCAL VARIABLE DECLARATIONS:
1091 : Real64 HWFlow; // hot water flow [kg/s]
1092 : Real64 CWFlow; // cold water flow [kg/s]
1093 : Real64 QPriOnly; // unit output with no zone coils active
1094 : Real64 ErrTolerance;
1095 :
1096 0 : bool UnitOn = true;
1097 0 : Real64 PowerMet = 0.0;
1098 0 : Real64 InducRat = state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio;
1099 0 : int PriNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).PriAirInNode;
1100 0 : int SecNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).SecAirInNode;
1101 0 : int OutletNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode;
1102 0 : int HotControlNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWControlNode;
1103 0 : int HWOutletNode = DataPlant::CompData::getPlantComponent(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc).NodeNumOut;
1104 0 : int ColdControlNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWControlNode;
1105 0 : int CWOutletNode = DataPlant::CompData::getPlantComponent(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc).NodeNumOut;
1106 0 : Real64 PriAirMassFlow = state.dataLoopNodes->Node(PriNode).MassFlowRateMaxAvail;
1107 0 : Real64 SecAirMassFlow = InducRat * PriAirMassFlow;
1108 0 : Real64 QToHeatSetPt = state.dataZoneEnergyDemand->ZoneSysEnergyDemand(ZoneNum).RemainingOutputReqToHeatSP;
1109 0 : Real64 QToCoolSetPt = state.dataZoneEnergyDemand->ZoneSysEnergyDemand(ZoneNum).RemainingOutputReqToCoolSP;
1110 : // On the first HVAC iteration the system values are given to the controller, but after that
1111 : // the demand limits are in place and there needs to be feedback to the Zone Equipment
1112 :
1113 0 : Real64 MaxHotWaterFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxHotWaterFlow;
1114 0 : PlantUtilities::SetComponentFlowRate(
1115 0 : state, MaxHotWaterFlow, HotControlNode, HWOutletNode, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc);
1116 :
1117 0 : Real64 MinHotWaterFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinHotWaterFlow;
1118 0 : PlantUtilities::SetComponentFlowRate(
1119 0 : state, MinHotWaterFlow, HotControlNode, HWOutletNode, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc);
1120 :
1121 0 : Real64 MaxColdWaterFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxColdWaterFlow;
1122 0 : PlantUtilities::SetComponentFlowRate(
1123 0 : state, MaxColdWaterFlow, ColdControlNode, CWOutletNode, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc);
1124 :
1125 0 : Real64 MinColdWaterFlow = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MinColdWaterFlow;
1126 0 : PlantUtilities::SetComponentFlowRate(
1127 0 : state, MinColdWaterFlow, ColdControlNode, CWOutletNode, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc);
1128 :
1129 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).availSched->getCurrentVal() <= 0.0) {
1130 0 : UnitOn = false;
1131 : }
1132 0 : if (PriAirMassFlow <= HVAC::SmallMassFlow) {
1133 0 : UnitOn = false;
1134 : }
1135 :
1136 : // Set the unit's air inlet nodes mass flow rates
1137 0 : state.dataLoopNodes->Node(PriNode).MassFlowRate = PriAirMassFlow;
1138 0 : state.dataLoopNodes->Node(SecNode).MassFlowRate = SecAirMassFlow;
1139 : // initialize the water inlet nodes to minimum
1140 : // fire the unit at min water flow
1141 0 : CalcFourPipeIndUnit(state, IUNum, FirstHVACIteration, ZoneNodeNum, MinHotWaterFlow, MinColdWaterFlow, QPriOnly);
1142 : // the load to be met by the secondary air stream coils is QZnReq-PowerMet
1143 :
1144 0 : if (UnitOn) {
1145 :
1146 0 : int SolFlag = 0;
1147 0 : if (QToHeatSetPt - QPriOnly > HVAC::SmallLoad) {
1148 : // heating coil
1149 : // check that it can meet the load
1150 0 : CalcFourPipeIndUnit(state, IUNum, FirstHVACIteration, ZoneNodeNum, MaxHotWaterFlow, MinColdWaterFlow, PowerMet);
1151 0 : if (PowerMet > QToHeatSetPt + HVAC::SmallLoad) {
1152 0 : ErrTolerance = state.dataHVACSingleDuctInduc->IndUnit(IUNum).HotControlOffset;
1153 : auto f = // (AUTO_OK_LAMBDA)
1154 0 : [&state, IUNum, FirstHVACIteration, ZoneNodeNum, MinColdWaterFlow, QToHeatSetPt, QPriOnly, PowerMet](Real64 const HWFlow) {
1155 : Real64 UnitOutput;
1156 0 : CalcFourPipeIndUnit(state, IUNum, FirstHVACIteration, ZoneNodeNum, HWFlow, MinColdWaterFlow, UnitOutput);
1157 0 : return (QToHeatSetPt - UnitOutput) / (PowerMet - QPriOnly);
1158 0 : };
1159 0 : General::SolveRoot(state, ErrTolerance, SolveMaxIter, SolFlag, HWFlow, f, MinHotWaterFlow, MaxHotWaterFlow);
1160 0 : if (SolFlag == -1) {
1161 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWCoilFailNum1 == 0) {
1162 0 : ShowWarningMessage(state,
1163 0 : format("SimFourPipeIndUnit: Hot water coil control failed for {}=\"{}\"",
1164 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1165 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
1166 0 : ShowContinueErrorTimeStamp(state, "");
1167 0 : ShowContinueError(state, format(" Iteration limit [{}] exceeded in calculating hot water mass flow rate", SolveMaxIter));
1168 : }
1169 0 : ShowRecurringWarningErrorAtEnd(
1170 : state,
1171 0 : format("SimFourPipeIndUnit: Hot water coil control failed (iteration limit [{}]) for {}=\"{}\"",
1172 : SolveMaxIter,
1173 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1174 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name),
1175 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWCoilFailNum1);
1176 0 : } else if (SolFlag == -2) {
1177 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWCoilFailNum2 == 0) {
1178 0 : ShowWarningMessage(state,
1179 0 : format("SimFourPipeIndUnit: Hot water coil control failed (maximum flow limits) for {}=\"{}\"",
1180 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1181 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
1182 0 : ShowContinueErrorTimeStamp(state, "");
1183 0 : ShowContinueError(state, "...Bad hot water maximum flow rate limits");
1184 0 : ShowContinueError(state, format("...Given minimum water flow rate={:.3R} kg/s", MinHotWaterFlow));
1185 0 : ShowContinueError(state, format("...Given maximum water flow rate={:.3R} kg/s", MaxHotWaterFlow));
1186 : }
1187 0 : ShowRecurringWarningErrorAtEnd(state,
1188 0 : "SimFourPipeIndUnit: Hot water coil control failed (flow limits) for " +
1189 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType + "=\"" +
1190 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name + "\"",
1191 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWCoilFailNum2,
1192 : MaxHotWaterFlow,
1193 : MinHotWaterFlow,
1194 : _,
1195 : "[kg/s]",
1196 : "[kg/s]");
1197 : }
1198 : }
1199 0 : } else if (QToCoolSetPt - QPriOnly < -HVAC::SmallLoad) {
1200 : // cooling coil
1201 : // check that it can meet the load
1202 0 : CalcFourPipeIndUnit(state, IUNum, FirstHVACIteration, ZoneNodeNum, MinHotWaterFlow, MaxColdWaterFlow, PowerMet);
1203 0 : if (PowerMet < QToCoolSetPt - HVAC::SmallLoad) {
1204 0 : ErrTolerance = state.dataHVACSingleDuctInduc->IndUnit(IUNum).ColdControlOffset;
1205 : auto f = // (AUTO_OK_LAMBDA)
1206 0 : [&state, IUNum, FirstHVACIteration, ZoneNodeNum, MinHotWaterFlow, QToCoolSetPt, QPriOnly, PowerMet](Real64 const CWFlow) {
1207 : Real64 UnitOutput;
1208 0 : CalcFourPipeIndUnit(state, IUNum, FirstHVACIteration, ZoneNodeNum, MinHotWaterFlow, CWFlow, UnitOutput);
1209 0 : return (QToCoolSetPt - UnitOutput) / (PowerMet - QPriOnly);
1210 0 : };
1211 0 : General::SolveRoot(state, ErrTolerance, SolveMaxIter, SolFlag, CWFlow, f, MinColdWaterFlow, MaxColdWaterFlow);
1212 0 : if (SolFlag == -1) {
1213 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWCoilFailNum1 == 0) {
1214 0 : ShowWarningMessage(state,
1215 0 : format("SimFourPipeIndUnit: Cold water coil control failed for {}=\"{}\"",
1216 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1217 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
1218 0 : ShowContinueErrorTimeStamp(state, "");
1219 0 : ShowContinueError(state,
1220 0 : format(" Iteration limit [{}] exceeded in calculating cold water mass flow rate", SolveMaxIter));
1221 : }
1222 0 : ShowRecurringWarningErrorAtEnd(state,
1223 0 : format("SimFourPipeIndUnit: Cold water coil control failed (iteration limit [{}]) for {}=\"{}",
1224 : SolveMaxIter,
1225 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1226 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name),
1227 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWCoilFailNum1);
1228 0 : } else if (SolFlag == -2) {
1229 0 : if (state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWCoilFailNum2 == 0) {
1230 0 : ShowWarningMessage(state,
1231 0 : format("SimFourPipeIndUnit: Cold water coil control failed (maximum flow limits) for {}=\"{}\"",
1232 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType,
1233 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name));
1234 0 : ShowContinueErrorTimeStamp(state, "");
1235 0 : ShowContinueError(state, "...Bad cold water maximum flow rate limits");
1236 0 : ShowContinueError(state, format("...Given minimum water flow rate={:.3R} kg/s", MinColdWaterFlow));
1237 0 : ShowContinueError(state, format("...Given maximum water flow rate={:.3R} kg/s", MaxColdWaterFlow));
1238 : }
1239 0 : ShowRecurringWarningErrorAtEnd(state,
1240 0 : "SimFourPipeIndUnit: Cold water coil control failed (flow limits) for " +
1241 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).UnitType + "=\"" +
1242 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).Name + "\"",
1243 0 : state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWCoilFailNum2,
1244 : MaxColdWaterFlow,
1245 : MinColdWaterFlow,
1246 : _,
1247 : "[kg/s]",
1248 : "[kg/s]");
1249 : }
1250 : }
1251 : } else {
1252 0 : CalcFourPipeIndUnit(state, IUNum, FirstHVACIteration, ZoneNodeNum, MinHotWaterFlow, MinColdWaterFlow, PowerMet);
1253 : }
1254 :
1255 : } else {
1256 : // unit off
1257 0 : CalcFourPipeIndUnit(state, IUNum, FirstHVACIteration, ZoneNodeNum, MinHotWaterFlow, MinColdWaterFlow, PowerMet);
1258 : }
1259 0 : state.dataLoopNodes->Node(OutletNode).MassFlowRateMax = state.dataHVACSingleDuctInduc->IndUnit(IUNum).MaxTotAirMassFlow;
1260 :
1261 : // At this point we are done. There is no output to report or pass back up: the output provided is calculated
1262 : // one level up in the calling routine SimZoneAirLoopEquipment. All the inlet and outlet flow rates and
1263 : // conditions have been set by CalcFourPipeIndUnit either explicitly or as a result of the simple component calls.
1264 0 : }
1265 :
1266 0 : void CalcFourPipeIndUnit(EnergyPlusData &state,
1267 : int const IUNum, // Unit index
1268 : bool const FirstHVACIteration, // flag for 1st HVAV iteration in the time step
1269 : int const ZoneNode, // zone node number
1270 : Real64 const HWFlow, // hot water flow (kg/s)
1271 : Real64 const CWFlow, // cold water flow (kg/s)
1272 : Real64 &LoadMet // load met by unit (watts)
1273 : )
1274 : {
1275 :
1276 : // SUBROUTINE INFORMATION:
1277 : // AUTHOR Fred Buhl
1278 : // DATE WRITTEN June 2004
1279 :
1280 : // PURPOSE OF THIS SUBROUTINE:
1281 : // Simulate the components making up the 4 pipe induction unit.
1282 :
1283 : // METHODOLOGY EMPLOYED:
1284 : // Simulates the unit components sequentially in the air flow direction.
1285 :
1286 : // SUBROUTINE LOCAL VARIABLE DECLARATIONS:
1287 : int OutletNode; // unit air outlet node
1288 : int PriNode; // unit primary air inlet node
1289 : int HotControlNode; // the hot water inlet node
1290 : int ColdControlNode; // the cold water inlet node
1291 : Real64 PriAirMassFlow; // primary air mass flow rate [kg/s]
1292 : Real64 SecAirMassFlow; // secondary air mass flow rate [kg/s]
1293 : Real64 TotAirMassFlow; // total air mass flow rate [kg/s]
1294 : Real64 InducRat; // induction ratio
1295 : Real64 mdotHW; // local temporary hot water flow rate [kg/s]
1296 : Real64 mdotCW; // local temporary cold water flow rate [kg/s]
1297 : int HWOutletNode;
1298 : int CWOutletNode;
1299 :
1300 0 : PriNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).PriAirInNode;
1301 0 : OutletNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).OutAirNode;
1302 0 : PriAirMassFlow = state.dataLoopNodes->Node(PriNode).MassFlowRateMaxAvail;
1303 0 : InducRat = state.dataHVACSingleDuctInduc->IndUnit(IUNum).InducRatio;
1304 0 : SecAirMassFlow = InducRat * PriAirMassFlow;
1305 0 : TotAirMassFlow = PriAirMassFlow + SecAirMassFlow;
1306 0 : HotControlNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWControlNode;
1307 0 : HWOutletNode = DataPlant::CompData::getPlantComponent(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc).NodeNumOut;
1308 :
1309 0 : ColdControlNode = state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWControlNode;
1310 0 : CWOutletNode = DataPlant::CompData::getPlantComponent(state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc).NodeNumOut;
1311 :
1312 0 : mdotHW = HWFlow;
1313 0 : PlantUtilities::SetComponentFlowRate(state, mdotHW, HotControlNode, HWOutletNode, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HWPlantLoc);
1314 :
1315 : // Node(HotControlNode)%MassFlowRate = HWFlow
1316 :
1317 0 : mdotCW = CWFlow;
1318 0 : PlantUtilities::SetComponentFlowRate(state, mdotCW, ColdControlNode, CWOutletNode, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CWPlantLoc);
1319 : // Node(ColdControlNode)%MassFlowRate = CWFlow
1320 :
1321 0 : WaterCoils::SimulateWaterCoilComponents(
1322 0 : state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil, FirstHVACIteration, state.dataHVACSingleDuctInduc->IndUnit(IUNum).HCoil_Num);
1323 0 : WaterCoils::SimulateWaterCoilComponents(
1324 0 : state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil, FirstHVACIteration, state.dataHVACSingleDuctInduc->IndUnit(IUNum).CCoil_Num);
1325 0 : MixerComponent::SimAirMixer(
1326 0 : state, state.dataHVACSingleDuctInduc->IndUnit(IUNum).MixerName, state.dataHVACSingleDuctInduc->IndUnit(IUNum).Mixer_Num);
1327 0 : LoadMet = TotAirMassFlow * Psychrometrics::PsyDeltaHSenFnTdb2W2Tdb1W1(state.dataLoopNodes->Node(OutletNode).Temp,
1328 0 : state.dataLoopNodes->Node(OutletNode).HumRat,
1329 0 : state.dataLoopNodes->Node(ZoneNode).Temp,
1330 0 : state.dataLoopNodes->Node(ZoneNode).HumRat);
1331 0 : }
1332 :
1333 0 : bool FourPipeInductionUnitHasMixer(EnergyPlusData &state, std::string_view CompName) // component (mixer) name
1334 : {
1335 :
1336 : // FUNCTION INFORMATION:
1337 : // AUTHOR Linda Lawrie
1338 : // DATE WRITTEN September 2011
1339 :
1340 : // PURPOSE OF THIS FUNCTION:
1341 : // Given a mixer name, this routine determines if that mixer is found on PIUnits.
1342 :
1343 0 : if (state.dataHVACSingleDuctInduc->GetIUInputFlag) {
1344 0 : GetIndUnits(state);
1345 0 : state.dataHVACSingleDuctInduc->GetIUInputFlag = false;
1346 : }
1347 :
1348 0 : if (state.dataHVACSingleDuctInduc->NumIndUnits > 0) {
1349 0 : int ItemNum = Util::FindItemInList(CompName, state.dataHVACSingleDuctInduc->IndUnit, &IndUnitData::MixerName);
1350 0 : if (ItemNum > 0) {
1351 0 : return true;
1352 : }
1353 : }
1354 :
1355 0 : return false;
1356 : }
1357 :
1358 0 : void IndUnitData::ReportIndUnit(EnergyPlusData &state)
1359 : {
1360 : // set zone OA volume flow rate
1361 0 : this->CalcOutdoorAirVolumeFlowRate(state);
1362 0 : }
1363 :
1364 0 : void IndUnitData::CalcOutdoorAirVolumeFlowRate(EnergyPlusData &state)
1365 : {
1366 : // calculates zone outdoor air volume flow rate using the supply air flow rate and OA fraction
1367 0 : if (this->AirLoopNum > 0) {
1368 0 : this->OutdoorAirFlowRate = (state.dataLoopNodes->Node(this->PriAirInNode).MassFlowRate / state.dataEnvrn->StdRhoAir) *
1369 0 : state.dataAirLoop->AirLoopFlow(this->AirLoopNum).OAFrac;
1370 : } else {
1371 0 : this->OutdoorAirFlowRate = 0.0;
1372 : }
1373 0 : }
1374 :
1375 1 : void IndUnitData::reportTerminalUnit(EnergyPlusData &state)
1376 : {
1377 : // populate the predefined equipment summary report related to air terminals
1378 1 : auto &orp = state.dataOutRptPredefined;
1379 1 : auto &adu = state.dataDefineEquipment->AirDistUnit(this->ADUNum);
1380 1 : if (!state.dataSize->TermUnitFinalZoneSizing.empty()) {
1381 1 : auto &sizing = state.dataSize->TermUnitFinalZoneSizing(adu.TermUnitSizingNum);
1382 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermMinFlow, adu.Name, sizing.DesCoolVolFlowMin);
1383 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermMinOutdoorFlow, adu.Name, sizing.MinOA);
1384 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermSupCoolingSP, adu.Name, sizing.CoolDesTemp);
1385 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermSupHeatingSP, adu.Name, sizing.HeatDesTemp);
1386 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermHeatingCap, adu.Name, sizing.DesHeatLoad);
1387 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermCoolingCap, adu.Name, sizing.DesCoolLoad);
1388 : }
1389 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermTypeInp, adu.Name, this->UnitType);
1390 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermPrimFlow, adu.Name, this->MaxPriAirMassFlow);
1391 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermSecdFlow, adu.Name, this->MaxSecAirMassFlow);
1392 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermMinFlowSch, adu.Name, "n/a");
1393 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermMaxFlowReh, adu.Name, "n/a");
1394 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermMinOAflowSch, adu.Name, "n/a");
1395 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermHeatCoilType, adu.Name, this->HCoilType);
1396 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermCoolCoilType, adu.Name, this->CCoilType);
1397 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermFanType, adu.Name, "n/a");
1398 1 : OutputReportPredefined::PreDefTableEntry(state, orp->pdchAirTermFanName, adu.Name, "n/a");
1399 1 : }
1400 :