************* All Return Air Paths passed integrity testing
************* No node connection errors were found.
************* Beginning Simulation
+ ** Warning ** CalcEquipmentFlowRates: Target water temperature is greater than the hot water temperature
+ ** ~~~ ** During Warmup, Environment=MIAMI INTL AP ANN HTG 99.6% CONDNS DB, at Simulation time=01/21 05:00 - 05:15
+ ** ~~~ ** ...target water temperature = 60.000 C
+ ** ~~~ ** ...hot water temperature = 51.667 C
+ ** ~~~ ** ...Note: target water temperature should be less than or equal to the hot water temperature
+ ** ~~~ ** ...Target water temperature should be less than or equal to the hot water temperature. Verify temperature setpoints and schedules.
+ ** Severe ** CheckWarmupConvergence: Loads Initialization, Zone="SPACE5-1" did not converge after 25 warmup days.
+ ** ~~~ ** See Warmup Convergence Information in .eio file for details.
+ ** ~~~ ** ...Environment(SizingPeriod)="MIAMI INTL AP ANN HTG 99.6% CONDNS DB"
+ ** ~~~ ** ..Max Temp Comparison = 9.73E-005 vs Temperature Convergence Tolerance=0.40 - Pass Convergence
+ ** ~~~ ** ..Min Temp Comparison = 5.85E-003 vs Temperature Convergence Tolerance=0.40 - Pass Convergence
+ ** ~~~ ** ..Max Heat Load Comparison = 4.2136E-002 vs Loads Convergence Tolerance=4.00E-002 - Fail Convergence
+ ** ~~~ ** ..Max Cool Load Comparison = 8.1106E-006 vs Loads Convergence Tolerance=4.00E-002 - Pass Convergence
************* Simulation Error Summary *************
************* There are 1 unused schedules in input.
************* There are 1 unused week schedules in input.
************* There are 1 unused day schedules in input.
************* Use Output:Diagnostics,DisplayUnusedSchedules; to see them.
- ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
+ *************
+ ************* ===== Recurring Error Summary =====
+ ************* The following recurring error messages occurred.
+ *************
+ ************* ** Warning ** SHOWERS" - Target water temperature should be less than or equal to the hot water temperature error continues...
+ ************* ** ~~~ ** This error occurred 28399 total times;
+ ************* ** ~~~ ** during Warmup 26415 times;
+ ************* ** ~~~ ** during Sizing 0 times.
+ ************* ** ~~~ ** Max=59.97187 Min=7.156259
+ *************
+ *************
+ ************* ===== Final Error Summary =====
+ ************* The following error categories occurred. Consider correcting or noting.
+ ************* Loads Initialization did not Converge
+ ************* ..1) very high thermal mass such as very thick concrete (solution: increase max number of warmup
+ ************* .. days in the BUILDING object);
+ ************* ..2) moderate mass and inadequate space conditioning such that the building keeps getting warmer
+ ************* .. and warmer on successive days (solution: add HVAC, check building thermal properties,
+ ************* .. check if infiltration is included, make sure HVAC properly controlled);
+ ************* ..3) a soil layer modeled below the concrete slab - (solution remove this layer and read about
+ ************* .. ground temperatures in the Auxiliary Programs document).
+ ************* ..4) unreasonable (too small) limits in the BUILDING object for temperature (.4 default) or
+ ************* .. loads tolerances (.04 default)
+ *************
+ ************* EnergyPlus Warmup Error Summary. During Warmup: 1 Warning; 1 Severe Errors.
************* EnergyPlus Sizing Error Summary. During Sizing: 0 Warning; 0 Severe Errors.