--- 
+++ 
@@ -9,10 +9,47 @@
    ************* All Return Air Paths passed integrity testing
    ************* No node connection errors were found.
    ************* Beginning Simulation
+   ** Warning ** CalcEquipmentFlowRates: Target water temperature is greater than the hot water temperature
+   **   ~~~   **  During Warmup, Environment=MIAMI INTL AP ANN HTG 99.6% CONDNS DB, at Simulation time=01/21 05:00 - 05:15
+   **   ~~~   ** ...target water temperature       = 60.000 C
+   **   ~~~   ** ...hot water temperature       = 51.667 C
+   **   ~~~   ** ...Note: target water temperature should be less than or equal to the hot water temperature
+   **   ~~~   ** ...Target water temperature should be less than or equal to the hot water temperature. Verify temperature setpoints and schedules.
+   ** Severe  ** CheckWarmupConvergence: Loads Initialization, Zone="SPACE5-1" did not converge after 25 warmup days.
+   **   ~~~   ** See Warmup Convergence Information in .eio file for details.
+   **   ~~~   ** ...Environment(SizingPeriod)="MIAMI INTL AP ANN HTG 99.6% CONDNS DB"
+   **   ~~~   ** ..Max Temp Comparison = 9.73E-005 vs Temperature Convergence Tolerance=0.40 - Pass Convergence
+   **   ~~~   ** ..Min Temp Comparison = 5.85E-003 vs Temperature Convergence Tolerance=0.40 - Pass Convergence
+   **   ~~~   ** ..Max Heat Load Comparison = 4.2136E-002 vs Loads Convergence Tolerance=4.00E-002 - Fail Convergence
+   **   ~~~   ** ..Max Cool Load Comparison = 8.1106E-006 vs Loads Convergence Tolerance=4.00E-002 - Pass Convergence
    ************* Simulation Error Summary *************
    ************* There are 1 unused schedules in input.
    ************* There are 1 unused week schedules in input.
    ************* There are 1 unused day schedules in input.
    ************* Use Output:Diagnostics,DisplayUnusedSchedules; to see them.
-   ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
+   *************
+   ************* ===== Recurring Error Summary =====
+   ************* The following recurring error messages occurred.
+   *************
+   *************  ** Warning ** SHOWERS" - Target water temperature should be less than or equal to the hot water temperature error continues...
+   *************  **   ~~~   **   This error occurred 28399 total times;
+   *************  **   ~~~   **   during Warmup 26415 times;
+   *************  **   ~~~   **   during Sizing 0 times.
+   *************  **   ~~~   **   Max=59.97187  Min=7.156259
+   *************
+   *************
+   ************* ===== Final Error Summary =====
+   ************* The following error categories occurred.  Consider correcting or noting.
+   ************* Loads Initialization did not Converge
+   ************* ..1) very high thermal mass such as very thick concrete (solution: increase max number of warmup
+   ************* ..   days in the BUILDING object);
+   ************* ..2) moderate mass and inadequate space conditioning such that the building keeps getting warmer
+   ************* ..   and warmer on successive days (solution: add HVAC, check building thermal properties,
+   ************* ..   check if infiltration is included, make sure HVAC properly controlled);
+   ************* ..3) a soil layer modeled below the concrete slab - (solution remove this layer and read about
+   ************* ..   ground temperatures in the Auxiliary Programs document).
+   ************* ..4) unreasonable (too small) limits in the BUILDING object for temperature (.4 default) or
+   ************* ..   loads tolerances (.04 default)
+   *************
+   ************* EnergyPlus Warmup Error Summary. During Warmup: 1 Warning; 1 Severe Errors.
    ************* EnergyPlus Sizing Error Summary. During Sizing: 0 Warning; 0 Severe Errors.